Register 0x1003 low
Actual state of detector
Warning code encrypted ( BIT VALUE ):
0x00 | NO ALARM |
0x01 | FAULT |
0x02 | THRESHOLD1 |
0x04 | THRESHOLD 2 |
0x08 | THRESHOLD 3 |
0x10 | OVERRANGE |
0x20 | Internal Use |
0x40 | Internal Use |
0x80 | Internal Use |
If the bits from 0-4 are equal to zero, the detector is in the normal operating state
Register 0x1003 high
Indicates the error state of detector error code encrypted:
0x00 | NO_ERRORS |
0x01 | HEATING |
0x02 | E2PROM_ERROR |
0x03 | FLASH_ERROR |
0x04 | RAM_ERROR |
0x05 | VCC_ERROR |
0x08 | VGND_ERROR |
0x09 | SEN S OR_ERROR |
0x0A | E2PROM_CKSM_ERROR |
0x0B | CHANGE_SENSOR |
0x0D | ANALOG_OUT_ERROR_4_20ma 0x0C VGND_ERROR |
0x0E | ADC_ERROR |
Zakres sygnałów alarmowych dla czujników C3-NET